The “P” version of the I-7016 module is another milestone in the development of the I-7016 series, and is a testament to excellence by the R&D team at ICP DAS. The I-7016P is specifically designed for long-distance strain gauge measurement, and provides 1 Digital Input channel as a 50 Hz event counter and 4 Digital Output channels that can act as high or low alarms. The I-7016P also features 3000 VDC intra-module isolation.
Features:
- Long-distance Strain Gauge Measurement
- High Resolution: 16-bit
- Excitation Voltage Output : 0 ~ +10 V
- 50 Hz Event Counter (Digital Input)
- High/Low Alarm (Digital Output)
- 3000 VDC Intra-module Isolation
- Dual Watchdog
- Wide Operating Temperature Range: -25 to +75°C
| CPU Module |
| Watchdog Timer |
Yes, Module (1.6 Seconds), Communication (Programmable) |
| Display |
| Type |
5-Digit 7 Segment LED Display |
| Isolation |
| Intra-module Isolation |
3000 VDC |
| EMS Protection |
| EFT (IEC 61000-4-4) |
4 kV Contact for each Terminal 8 kV Air for Random Point |
| ESD (IEC 61000-4-2) |
+4 kV for Power Line |
| LED Indicators |
| Status |
1 x Power and Communication |
| Analog Input |
| Channels |
1 |
| Type |
Strain Gauge |
| Sensor Type |
Full-Bridge |
| Resolution |
16-bit |
| Accuracy |
+0.05% of FSR |
| Sampling Rate |
10 Hz |
| Input Impedance |
20 M? |
| Overvoltage Protection |
+5 VDC |
| Long Distance Measurement |
Yes |
| Digital Input/Counter |
| Channels |
1 |
| Type |
Dry Contact |
| Sink/Source (NPN/PNP) |
Source |
| ON Voltage Level |
Close to GND |
| OFF Voltage Level |
Open |
| Max. Counts |
16-bit |
| Frequency |
50 Hz |
| Input Impedance |
3 k? |
| Overvoltage Protection |
+30 VDC |
| Digital Output |
| Channels |
4 |
| Type |
Open Collector |
| Sink/Source (NPN/PNP) |
Sink |
| Load Voltage |
+3.5 ~ +50 VDC |
| Max. Load Current |
30 mA/Channel |
| Power on Value |
Yes |
| Safe Value |
Yes |
| Excitation Voltage Output |
| Channels |
1 |
| Range |
0 ~ +10 V |
| Resolution |
16-bit |
| Accuracy |
+0.05% |
| Max. Load Current |
40 mA |
| Power on Value |
Yes |
| COM Ports |
| Ports |
1 x RS-485 |
| Baud Rate |
1200 to 115200 bps |
| Data Format |
N, 8, 1 |
| Protocol |
DCON |
| Power |
| Reverse Polarity Protection |
Yes |
| Input Range |
+10 ~ +30 VDC |
| Consumption |
1.3 W |
| Mechanical |
| Dimensions (mm) |
123 x 72 x 35 (W x L x H) |
| Installation |
DIN-Rail |
| Environmental |
| Operating Temperature |
-25 ~ +75 °C |
| Storage Temperature |
-40 ~ +85 °C |
| Humidity |
10 ~ 95% RH, Non-condensing |